Coolant and Temperature Control Couplings
Couplings and Disconnects
Coolant and temperature control couplings join the water-carrying sections of a data centre wherever a connection has to stay releasable: at the coolant distribution unit, the heat exchanger, the dry cooler and the rack supply lines. Unlike compressed air couplings they are built for liquid standing permanently in the line, with shut-off valves in one or both halves and seals that survive a water-glycol mixture. The category holds 160 items from Nitto Kohki, Riegler and our own brand.
The core comes from the Nitto series SP-A Cupla in sizes 2S-A through 6P-A, TSP Cupla from 1TSH to 8TSF, the hot water HW Cupla range and the short-bodied Compact Cupla such as CO-40PN and CO-60PN. Ports run from Rc 1/4 and R 1/4 up to R 1, in brass or stainless steel. For a closed IT circuit the stainless types are the right choice; brass only where the entire circuit stays within one material family.
SP-A Cupla, TSP Cupla, HW Cupla and Compact Cupla
| Criterion | SP-A Cupla | TSP Cupla | HW Cupla | Compact Cupla |
|---|---|---|---|---|
| Sizes listed | 2S-A, 3S-A, 3P-A, 4P-A, 6P-A | 1TSH, 2TSM, 2TSF, 2TSH, 4TPM, 6TSF, 8TSF | HW-3P-M | CO-1SF, CO-40PN, CO-60PN |
| Ports | R 3/8, R 1/2, R 3/4 | Rc 1/4, R 1/4, Rc 1/2, R 3/4, R 1 | Rc 3/8 | R 1/8, push-fit |
| Materials | stainless steel, brass | stainless steel, brass | brass | stainless steel |
| Body | standard length, threaded | standard length, wide size range | hot water range | short body, small installed length |
| Installed at | distribution units and supply lines | heat exchangers, dry coolers, ring mains | hot water sections | densely populated manifolds |
| IT circuit | stainless unrestricted | stainless unrestricted | only in an all-brass circuit | unrestricted |
- Connecting rack supply lines to the coolant distribution unit
- Releasable joints at heat exchangers, dry coolers and pump sets
- Hot water sections of heat recovery systems
- Rebuilding and extending cooling circuits without welding or brazing
- Manifolds on a tight port pitch where installed length matters
- Same-material connection to stainless steel pipework and manifolds