Filtration and Loop Cleaning
Data Center
Filtration in a closed water-glycol loop keeps particles away from the narrow channels of cold plates. A channel a few tenths of a millimetre wide is blocked by assembly swarf, seal abrasion and corrosion products long before temperature monitoring reacts, and pressure loss rises first. This branch groups 469 items into four families: strainers and screens from DN 8 to DN 32 with mesh sizes of 0.05 to 1.0 mm, side-stream filters and filter housings, filter elements from 0.01 to 40 microns, and separators. Brands are Riegler, Fluidics equipment, E.MC, Resideo Braukmann and Cejn.
Sizing follows two stages. A coarse screen with a mesh of 0.5 to 1.0 mm protects the pump and the control valves against commissioning debris, while a fine side-stream filter rated 5 microns keeps the continuous particle load low. Material choice is fixed for the IT loop: stainless steel, PVDF, PP, PE, PTFE, POM and PVC are unrestricted, brass, gunmetal and sintered bronze only with a single-metal pairing, galvanised steel and aluminium not at all.
Categories




The four families compared - strainers, side-stream filters, filter elements and separators
| Criterion | Strainers and screens | Side-stream filters and housings | Filter elements | Separators |
|---|---|---|---|---|
| Function | retention of coarse particles | continuous cleaning of a partial flow | wear part inside the housing | bubbles, sludge and water |
| Grade | mesh 0.05 to 1.0 mm | fine and micro filter stages | 0.01 to 40 microns | no mesh rating |
| Connection | G 1/4 to G 1 1/4, DN 8 to DN 32 | G 1/8 to G 3/8 | sizes 1 to 3, DF20, DF30 | tube 22 and 28 mm |
| Materials | brass, gunmetal, screen 1.4408 | PA 66 GF60, zinc die-cast Z410 | sintered PE, sintered bronze, borosilicate-POM | POM, brass |
| Service | remove and flush the screen | change the element in the side stream | replace on differential pressure | drain the collecting chamber |
| Items | 252 | 206 | 9 | 2 |
- Secondary loop between coolant distribution unit and dry cooler
- Cold plate circuits with narrow channel cross sections
- Flushing and commissioning of new pipe runs
- Side-stream cleaning during operation without shutting the plant down
- Filling and service carts for water-glycol mixtures
- Retrofit of existing installations without a filter station