Mounting and Cable Management
Data Center
Mounting and cable management covers the parts that hold pipes, hoses and cables in place in the cooling loop of a data centre: pipe clamps to DIN 3015 in the light and heavy series, worm drive hose clamps, C section mounting rails, brackets and consoles, plus cable ties for the accompanying wiring. The branch holds 8,241 items from Stauff, Hydac, Norma, Riegler, Oetiker and Band-It. Clamp bodies cover pipe outside diameters from 10 mm to 65 mm, hose clamps clamping ranges from 10 mm to 110 mm.
In a water glycol loop the material pairing decides how long a fixing lasts. Clamp bodies in polypropylene and polyamide isolate the pipe electrically from the steelwork and damp vibration from pumps and flow. Hardware should be stainless steel, for example 1.4301 (W4) or 1.4401/1.4571 (W5); galvanised steel and aluminium are ruled out in a glycol loop, and brass belongs only where it meets brass or gunmetal in a single material pairing.
Categories




Pipe clamp, hose clamp, mounting rail and cable tie compared
| Criterion | Pipe clamp DIN 3015 | Hose clamp | Rail and console | Cable tie |
|---|---|---|---|---|
| Function | fixes the pipe to the structure | seals a hose end onto a barbed tail | carries and aligns the clamps | bundles and routes cables |
| Size range | sizes 1 to 7, 10 to 65 mm pipe OD | clamping range 10 to 110 mm | C rail 28 x 11 and 28 x 14 mm | band 3.6 and 4.8 mm, length 150 to 350 mm |
| Material in an IT loop | PP or PA body, stainless hardware | stainless 1.4301 (W4) or 1.4401/1.4571 (W5) | rail 1.4571, console A4 | polyamide 6.6 |
| Installation | weld plate, cover plate or mounting rail | worm drive, screwdriver or socket | bolted with channel nuts M 8 to M 12 | no tools, pack of 100 |
| Reusable | yes | yes | yes | single use, cut to release |
- water glycol pipework in the raised floor and below the ceiling
- header pipes ahead of the coolant distribution unit and at the rack manifold
- connections at pumps and heat exchangers where vibration enters the pipe
- hose sections on service lines and movable connections
- sensor and signal cables running alongside the pipe route
- retrofitting existing routes with twin clamps for two pipe levels