Facility Water System (FWS)

Data Center

The facility water system (FWS) is the outer loop of a data centre cooling installation. It picks up the heat of the inner loop, the technology cooling system, across a heat exchanger and rejects it to the surroundings. Dry coolers and free cooling modules, pump sets, buffer tanks and hydraulic separators, and the treatment of the circulating water all belong to this loop. The medium is water or a water-glycol mixture, and the glycol content drives both the required flow rate and the choice of wetted materials. This section describes what each assembly does in the loop; the matching range is currently being built up.

No articles are listed in this branch at present. The subcategories are already in place so that the intended scope of the facility loop is visible, together with the gaps that still exist today. Until the range is published, the sections below set out the selection criteria: the task each assembly performs in the loop, which materials hold up in a data centre water-glycol circuit, and what to watch for when components of different metals are combined.

Dry Coolers and Free Cooling ModulesHeat rejection to ambient air, free cooling at low outdoor temperature
Buffer Tanks and Hydraulic SeparatorsLoop water volume, hydraulic decoupling of source and load
Water Treatment, Softening, DemineralisationFill water conditioning, hardness and salt load kept out of the loop

Outer cooling loop - takes up the heat of the IT loop across a heat exchanger and rejects it to the surroundings
Water or water-glycol - glycol lowers the heat capacity, so the volume flow has to be raised accordingly
Materials without restriction - stainless steel, PVDF, PP, PE, PTFE, POM and PVC are suitable for permanent wetted service
Copper alloys only single-metal - brass, gunmetal, bronze and copper only where no mixed-metal installation results
Not for this loop - galvanised steel and aluminium, both erode in a glycol circuit and load it with sludge
Range under construction - the section currently describes the function of each assembly, listed goods will follow

Function and selection criteria per assembly

AssemblyFunction in the cooling loopWhat matters when selecting
Dry coolers and free cooling modulesReject the heat of the loop to ambient air and replace mechanical cooling as soon as the outdoor temperature is low enoughCapacity at the design point, air flow and sound level, wetted material, glycol content of the medium
Buffer tanks and hydraulic separatorsProvide water volume in the loop and decouple the source side from the load side hydraulicallyStorage volume, connection size and port arrangement, insulation, shell material
Water treatment, softening, demineralisationCondition fill and make-up water and keep hardness, dissolved salts and particles out of the loopRaw water quality on site, loop volume, process (filtration, softening, demineralisation), monitoring of water values

  • Data centres with air-cooled dry coolers and year-round free cooling
  • Colocation floors with strictly separated facility and IT loops
  • Retrofitting a free cooling branch onto existing chillers
  • Edge sites with compact outdoor heat rejection
  • Installations running water-glycol where frost protection is required outdoors
  • Refurbishment of older loops in which galvanised or mixed-metal sections are replaced