Labelling and Plant Documentation

Data Center

Labelling and plant documentation answer at the component itself what a line carries, in which direction it flows and which circuit it belongs to. In a data centre the flow and return of the water-glycol loop, chilled water, condensate and compressed air often run side by side through the same plant room, in redundant pairs and in identical pipe sizes. Anyone closing a valve or breaking a union has to know beforehand which of the parallel circuits is affected. Pipe marking to DIN 2403 with medium, flow direction and colour group provides that basis, supplemented by cable marking, labels and marking tapes.

This section currently describes the function of marking within the cooling loop; no products are listed yet and the range is being built up. What counts are carrier materials that withstand condensation, cleaning agents and permanent humidity in the plant room, and marking that remains exchangeable during modifications and leaves no adhesive residue on stainless steel, PVC or painted pipework.

⚡ Medium named in plain text - cooling water, condensate and compressed air stay distinguishable
↕ Flow direction as an arrow - flow and return identified without consulting the schematic
⚙ Colour group by medium - aqueous media in green, air in grey, recognised at a glance
✓ Exchangeable carriers - changes at the manifold can be updated without residue
⚠ Note on the glycol mixture - the loop medium is not potable water and has to be flagged
↻ One circuit number throughout - pipe, valve, sensor and cable carry the same designation

What is marked where

LevelCarrierInformation shownCheck before the intervention
PipeworkPipe marker to DIN 2403medium, flow direction, colour groupWhich of the parallel circuits is being isolated
Valve, pump, filterLabel or tag on the bodycircuit number, function, positionDoes the isolating device serve the same run
Cable and coreSlide-on marker, wrap-around labelsource, destination, power or control circuitAre both ends marked identically
Route and floorMarking and warning taperouting, restricted area, hazard pointIs the work area demarcated
Plant schematicDrawing and as-built recordcircuit, run, component numberDoes the installation match the record

  • Plant room with chiller, pump set and manifold
  • Risers and ceiling penetrations between plant room and white space
  • Connection of cooling manifold, CDU and rack in the white space
  • Free cooler and dry cooler on the roof
  • Emergency cooling loop, buffer tank and make-up line
  • Handover points between operator and service contractor