Measurement, Monitoring and Leak Detection

Data Center

Instrumentation supplies the values a data centre cooling loop is actually run on: supply and return pressure at pump and manifold, medium temperature before and after the heat exchanger, volume flow per rack or CDU and level in the expansion vessel. The range holds 4,254 items from Wika, Riegler, Stauff, Cejn, Nitto Kohki and Sang-A. It spans bourdon and capsule pressure gauges from 40 mm dial size, Pt100 and Pt1000 resistance thermometers with 4-20 mA output, flow switches from 0.1 to 110 l/min and level switches with guide tube lengths of 150 to 500 mm.

In a water-glycol loop the wetted material decides service life. Stainless steel 1.4571, 1.4305 and 1.4301 as well as CrNi steel cases are unrestricted. Brass and nickel-plated brass stay limited to single-material pairings, galvanised steel and aluminium have no place in an IT loop. On gauges the fill adds to this: glycerine damps pulsation from the circulating pump, stainless chemical versions take glycol mixtures permanently.

⚡ 4,254 items in nine groups - pressure, temperature, flow, level and test connections from one source
↕ -1 to 630 bar - from vacuum in the expansion vessel to the test point of a high pressure check
⚙ 4-20 mA standard signal - Pt1000 probes TR33 and TR36 connect to the BMS without a separate transmitter
✓ 1.4571 and 1.4305 throughout - wetted parts in stainless steel, suitable for water-glycol mixtures
📈 0.1 to 110 l/min in overlapping spans - flow switches for a single rack up to the header
🔧 Wika, Riegler and Stauff - gauges, thermometers and test equipment as the backbone of the range

Measured variables in the cooling loop - designs, spans and materials in the range

VariableDesigns in the rangeSpanWetted materialItems
PressureBourdon, glycerine filled, chemical and capsule gauges, 40 to 100 mm dial-1 to 250 bar, capsule from 25 mbarCrNi steel, 1.4571, brass3,621
TemperaturePt100 and Pt1000 resistance thermometers, bimetal thermometers-40 to +120 °C1.4571, 1.430169
FlowFlow meters and switches G 1"0.1 to 110 l/min1.4571, nickel-plated brass211
LevelLevel switches G 1/2" and G 1"guide tube 150 to 500 mm1.457116
Test connectionM 16x2 test points, test hoses, pressure test casesup to 630 bar, -20 to +200 °C1.4571, 1.4305301
Water quality and leakagecategories createdrange being built upopen0

  • supply and return monitoring on chillers, free coolers and dry coolers
  • flow verification per rack, CDU or manifold in a direct-to-chip loop
  • temperature spread across the heat exchanger between primary and secondary loop
  • level monitoring on expansion and storage vessels of the glycol loop
  • pressure testing and commissioning of new pipe sections via test points and test cases
  • recording of operating values for maintenance, acceptance and energy accounting