Solenoid and Motorised Control Valves

Shut-Off, Control and Safety Valves

Solenoid and motorised control valves open or close a cooling circuit on an electrical signal, without anyone having to reach the valve. That allows circuits to be released by temperature, changeover between free cooling and chiller, and a leaking section to be isolated from the control room. The group holds 298 items: two-way brass solenoid valves of the M and ZS series in G 3/4, G 1 and G 1 1/2, plus brass ball valves with a double-acting pneumatic actuator in Rp 3/8 and Rp 1/2. Brands: Fluidics equipment, E.MC, Riegler, Airtec and YPC.

Voltage is the first decision: stock covers 12, 24, 48, 115 and 230 V, each as a DC or AC version. The difference is not only electrical. The same series switches up to 16 bar on AC, while on DC the permitted differential pressure ends at 9 to 10 bar. All versions listed here are normally closed, so the circuit shuts on power failure. Clarify the seal variant before ordering: EPDM suits water-glycol, FKM belongs with oils.

⚡ Voltage and current type - 12, 24, 48, 115 and 230 V in stock, as DC and AC. The current type sets the permitted differential pressure of the same series.
↕ Check the differential pressure - AC versions are rated up to 16 bar, DC versions up to 9 or 10 bar. The vacuum range is covered down to minus 0.95 bar.
✓ Fail position - The valves listed are normally closed. On power failure the circuit shuts, which is what you want for leak isolation and what you must review for cooling duty.
⚙ Seal against the medium - Each series comes in two seal variants. EPDM is the right elastomer for water-glycol, FKM is intended for oils and fuels.
⚑ Actuated ball valve as alternative - Ball valves with a double-acting actuator in Rp 3/8 and Rp 1/2 also switch large cross sections and leave the full bore open.
↻ Connection size - G 3/4, G 1 and G 1 1/2 on the solenoid valves, Rp 3/8 and Rp 1/2 on the actuated ball valves.

Solenoid valve and actuated ball valve

CriterionTwo-way solenoid valve, ACTwo-way solenoid valve, DCBall valve with pneumatic actuator
Voltages in stock115 V, 230 V, 24 V AC, 48 V AC12 V, 24 V, 48 Vcontrol air, signal via pilot valve
Pressure range-0.95 to 16 bar-0.95 to 9 or 0 to 10 barper ball valve
ConnectionsG 3/4, G 1, G 1 1/2G 3/4, G 1, G 1 1/2Rp 3/8, Rp 1/2
De-energised positionclosed (NC)closed (NC)double-acting, holds its position
Flow pathseat valve, restrictedseat valve, restrictedfull bore

  • Temperature-led release of individual cooling circuits through the building management system
  • Changeover between free cooling and chiller over the course of the year
  • Remote isolation of a riser on a leak alarm
  • Automatic make-up of a closed circuit after a pressure drop
  • Cycling bypass lines for temperature control
  • Remote operation of large isolation points through ball valves with pneumatic actuators