Images are examples, some edited with AI. The technical data are authoritative. AI notice
DIN rail monitoring unit Perseus Industrial 310, 5 DI, 2 relays, 2 sensor ports, WLD-L, PoE - HW group 600931
Perseus Industrial 310 brings the Perseus monitoring and control platform to a 6-module DIN rail device. It combines 5 digital inputs with S0 pulse counting, 2 relays, 2 RJ11 sensor ports, a WLD-L port for leak location and RS-485 for Modbus/RTU, expandable with RTU expanders. Plain unit without power adapter or sensors, for distribution boards, technical rooms and industry.
- Specialist dealer since 2009
- Invoice payment for regular customers
- Worldwide shipping
- Technical questions clarified with the manufacturer
Description
In control cabinets and distribution boards, monitoring belongs next to the meters and breakers. Perseus Industrial 310 takes 6 modules on the DIN rail, reads up to 100 meters with 1000 variables and, through its WLD-L port, can also show where water is leaking.
Benefits
- Locate leaks, not just detect them: 4-pin WLD-L port for 1 type L location zone or 2 standard type A/B WLD zones.
- Direct energy meter connection: 5 digital inputs with pulse counters, S0 input to EN 62053-31 Class B.
- Scalable: DIN rail RTU expanders add digital inputs and relay outputs as the application requires.
- Third-party integration: RS-485 terminal with 12 V output for Modbus/RTU meters, UPS or air conditioning units.
- Local reaction: 2 relay outputs (max. 50 V, 1000 mA) switch ventilation, cooling or doors based on readings.
- Flexible power via PoE (250 mA), 12-30 V DC or -48 V DC.
Applications
- Sub-distribution boards and control cabinets with energy meters
- Technical rooms and infrastructure sites that need leak location
- Leak monitoring around CDUs, coolant lines and quick disconnects in liquid cooling
- Telecom cabinets and base stations
- Warehouses, pharmaceutical storage, greenhouses and machine monitoring
Compatibility
- HW group 1-Wire UNI sensors on the RJ11 ports
- HW group WLD sensing cables type A/B and type L location cables on the WLD-L port
- HW group DIN rail RTU expanders
- Meters API: HWg devices such as STE2 R2 via XML, plus devices using SNMP, Modbus/TCP, MQTT or Modbus/RTU
- Portal based on SensDesk technology and the HWg Monitor app for Android and iOS
Technical data
| Network | Ethernet RJ45, 10/100 Mbit/s, DHCP, IPv6 |
|---|---|
| Protocols | HTTP, HTTPS, WebSocket, SNMP v1 and v3, SNMP trap, SMTP with TLS, SNTP, XML, MQTT, Modbus/TCP, BACnet/TCP |
| Sensor ports | 2 x RJ11 for 1-Wire UNI sensors |
| RS-485 | 1 x terminal block with 12 V output, Modbus/RTU |
| Digital inputs | 5 x dry contact, with counters, S0 pulse input to EN 62053-31 Class B |
| Water leak detection | 1 x WLD-L port: 1 type L location zone or 2 type A/B zones |
| Relay outputs | 2 x relay, max. 50 V, 1000 mA |
| Capacity | up to 100 meters, 1000 variables, 32 MB data logger |
| Alerting | Email, SNMP trap, SMS and calls via external SMS gateway, up to 100 recipients each |
| Security | RADIUS (IEEE 802.1X), admin and user accounts, HTTPS with custom certificate |
| Power supply | 12-30 V DC via barrel jack (2.1/5.5 mm) or terminal block, -48 V DC via terminal block, PoE via RJ45 |
| Consumption | 500 mA at 12-30 V DC and -48 V DC, 250 mA at PoE |
| Operating conditions | -30 to +65 °C, 5-95 % RH |
| Dimensions and weight | 105 x 90 x 57 mm (W x H x D), 207 g |
| Housing and mounting | Plastic, DIN rail, 6 modules |
| Ingress protection | IP40 |
| Warranty | 24 months |
| Manufacturer part number | 600931 |
| Weight | 0.207 kg |
| Manufacturer | HW group |
| Hersteller-Nr | 600931 |
| Zolltarifnummer | 85176200 |
| GPSR Herstellerdaten | HW group s.r.o., Rumunská 26, CZ-120 00 Praha 2, www.hw-group.com |
| Artikelzustand | New |
| Artikel-Authentizität | Original product |
| Country of Manufacture | Czechia |
| Housing material | Plastic |
| Interface | Digital I/O, Ethernet, RS-485, 1-Wire |
| Protection rating | IP40 |
Scope of delivery
- Perseus Industrial 310 plain unit
- Not included: power adapter and sensors
Downloads
User Manual
Declaration of Conformity
Accessories
Water flood detector 1W-UNI 3m, spot detection with 4 contact pins, IP67, 3 m cable, RJ11 - HW group 600579
Item HWG-600579Power presence detector Power Detector 110-230 V AC, EU plug Type C, relay output for DI - HW group 600667
Item HWG-600667Wall plug power adapter 24 V DC, 1 A, EU plug, 2-pin terminal for Perseus Energy 242 - HW group 600900
Item HWG-600900RTU-Expander 1004 for Perseus, 10 digital inputs, 4 relay outputs, Modbus RTU, DIN rail - HW group 600927
Item HWG-600927RTU-Expander 2004 for Perseus, 20 digital inputs, 4 relay outputs, Modbus RTU, DIN rail - HW group 600928
Item HWG-600928RTU-Expander 3004 for Perseus, 30 digital inputs, 4 relay outputs, Modbus RTU, DIN rail - HW group 600929
Item HWG-600929RTU connection cable 0.15 m, RTU to RTU with two 4-pin connectors, for RTU Expander - HW group 600952
Item HWG-600952Show 1 more items
WLD sensing cable Type B set 2+2 m, 2 m sensing cable with 2 m connecting cable AB, ready to connect - HW group 600918
Item HWG-600918ESD version
DIN rail monitoring unit Perseus Industrial 315, LTE, 5 DI, 2 relays, WLD-L, RS-485, plain unit - HW group 600932
Item HWG-600932Questions about this item
Any other question?
Send us the item number and your question. We clarify technical details directly with the manufacturer and usually reply on the next working day. Ask a question