Images are examples, some edited with AI. The technical data are authoritative. AI notice
Flow sensor 5 to 100 l/min for liquids G1 IO-Link SFAW-100-TG1-E-PNLK-PNVBA-M12 - Festo 8036877
The flow sensor SFAW-100-TG1-E-PNLK-PNVBA-M12 is designed for flow rate and temperature of liquids between 5 l/min and 100 l/min. Outputs of the SFAW: two switching outputs, PNP or NPN selectable, plus analogue output 0 - 10 V, 4 - 20 mA, 1 - 5 V and IO-Link. Operating pressure 0 to 12 bar, connection female thread G1.
Available
- Specialist dealer since 2009
- Invoice payment for regular customers
- Worldwide shipping
- Technical questions clarified with the manufacturer
Description
With the Festo SFAW-100-TG1-E-PNLK-PNVBA-M12 you record flow rate and temperature within 5 to 100 l/min and evaluate the values on the device or in the controller.
Benefits
- Measuring range 5 to 100 l/min
- Measurement method Temperature: PT1000, Flow: Vortex
- Switching output 2 x PNP or 2 x NPN, switchable, analogue output 0 - 10 V, 4 - 20 mA, 1 - 5 V and IO-Link
- Operating pressure 0 to 12 bar, degree of protection IP65
Applications
Operating medium of the SFAW-100-TG1-E-PNLK-PNVBA-M12: liquid media, neutral fluids, water, flow direction P1 to P2, unidirectional. Typical tasks up to 100 l/min include monitoring cooling and process water circuits. The SFAW-100-TG1-E-PNLK-PNVBA-M12 runs on 18 to 30 V DC.
Technical data
| Type | SFAW-100-TG1-E-PNLK-PNVBA-M12 |
|---|---|
| Festo part number | 8036877 |
| Approval | RCM, c UL us - Listed (OL) |
| CE mark (see declaration of conformity) | To EU EMC Directive, to EU RoHS Directive |
| KC mark | KC-EMV |
| Note on materials | RoHS compliant |
| Measured variable | flow, temperature |
| Flow direction | P1 to P2, Unidirectional |
| Measurement method | Temperature: PT1000, Flow: Vortex |
| Start value for flow rate measuring range | 5 l/min |
| End value for flow rate measuring range | 100 l/min |
| Operating pressure | 0 to 12 bar |
| Note on operating pressure | max. 12 bar at 40 °C, max. 6 bar at 100 °C |
| Operating medium | Liquid media, Neutral fluids, Water |
| Note on operating and pilot medium | Compatibility of the medium with the wetted materials must be ensured |
| Media temperature | 0 to 90 °C |
| Ambient temperature | 0 to 50 °C |
| Nominal temperature | 23 °C |
| Accuracy temperature in ± °C | 2 °C |
| Temperature coefficient span in ± %FS/K | typ. ±0.05%FS/K |
| Switching output | 2 x PNP or 2 x NPN, switchable |
| Switching function | Window comparator, Threshold comparator, Freely programmable |
| Switching element function | NC or NO, switchable |
| Max. output current | 100 mA |
| Analogue output | 0 - 10 V, 4 - 20 mA, 1 - 5 V |
| Flow characteristic curve start value | 0 l/min |
| Flow characteristic curve end value | 100 l/min |
| Max. load resistance current output | 500 Ohm |
| Min. load resistance voltage output | 15 kOhm |
| Short circuit current rating | Yes |
| Overload protection | Available |
| Protocol | IO-Link |
| IO-Link, protocol version | Device V 1.1 |
| IO-Link, profile | Smart sensor profile |
| IO-Link, function classes | Teach channel, Diagnostics, Identification, Binary data channel (BDC), Process data variable (PDV) |
| IO-Link, communication mode | COM2 (38.4 kBaud) |
| IO-Link, SIO mode support | Yes |
| IO-Link, port type | A |
| IO-Link, process data width OUT | 0 bytes |
| IO-Link, process data width IN | 3 bytes |
| IO-Link, process data content IN | 1 bit BDC (volume monitoring), 14 bit PDV (measured flow value), 2 bit BDC (flow monitoring) |
| IO-Link, service data content IN | 32 bit measured volume value |
| IO-Link, minimum cycle time | 5 ms |
| IO-Link, data storage required | 500 Byte |
| Operational voltage range DC | 18 to 30 V |
| Reverse polarity protection | For all electrical connections |
| Electrical connection | M12x1, 5-pin, straight plug, A-coded |
| Max. cable length | 30 m, 20 m in IO-Link mode |
| Mounting position | Any |
| Fluid connection | Female thread G1 |
| Product weight | 400 g |
| Material housing | Reinforced PA |
| Material in contact with the medium | EPDM (perox.), ETFE, stainless steel, reinforced PA6T/6I |
| Displayable units | US gal, US gal/min, cft, cft/min, l, l/h, l/min, m3, °C, °F |
| Degree of protection | IP65 |
| Corrosion resistance class CRC | 3 - high corrosion stress |
| Weight | 0.48 kg |
| Manufacturer | Festo |
| Hersteller-Nr | SFAW-100-TG1-E-PNLK-PNVBA-M12 |
| EAN | 4052568285333 |
| Zolltarifnummer | 90261021 |
| GPSR Herstellerdaten | Festo Vertrieb GmbH&Co. KG, Festo Campus 1, DE-73734 Esslingen, festo.com |
| Artikelzustand | New |
| Artikel-Authentizität | Original product |
| Material | Polyamide (PA) |
| Thread | G 1 |
| Medientemperatur [°C] | 0 bis 90 |
| Operating voltage | 18-30 V |
| Series | SFAW |
| Betriebsdruck max [bar] | 12 |
| Pneumatic connection | G1 |
| Protection rating | IP65 |
| Temperaturbereich | 0-50 °C |
| Temperature (max.) | 50 |
Downloads
Accessories
Connecting cable M8x1, 3-pin, 3-wire, socket, angled, open end 2.5 m SIM-M8-3WD-2,5-PSL-PU - Festo 159424
Item FES-159424Flow sensor 5 to 100 l/min for liquids G3/4 IO-Link SFAW-100-TG34-E-PNLK-PNVBA-M12 - Festo 8036875
Item FES-8036875Flow sensor 5 to 100 l/min for liquids IO-Link SFAW-100-X-E-PNLK-PNVBA-M12 - Festo 8036889
Item FES-8036889Flow sensor 5 to 100 l/min for liquids G3/4 IO-Link SFAW-100T-TG34-E-PNLK-PNVBA - Festo 8036876
Item FES-8036876Flow sensor 5 to 100 l/min for liquids G1 IO-Link SFAW-100T-TG1-E-PNLK-PNVBA-M12 - Festo 8036878
Item FES-8036878Questions about this item
Any other question?
Send us the item number and your question. We clarify technical details directly with the manufacturer and usually reply on the next working day.