Images are examples, some edited with AI. The technical data are authoritative. AI notice
Analogue output module 4 outputs IP20 CPX-E-4AO-U-I - Festo 4080494
Festo analogue output module CPX-E-4AO-U-I at a glance: 4 outputs, degree of protection IP20, grid dimension 18.9 mm. As part of the CPX-E series, the module extends the periphery of a controller with additional channels.
- Specialist dealer since 2009
- Invoice payment for regular customers
- Worldwide shipping
- Technical questions clarified with the manufacturer
Description
The CPX-E-4AO-U-I belongs to the Festo CPX-E series. As part of the CPX-E series, the module extends the periphery of a controller with additional channels.
Benefits
- 4 outputs
- Degree of protection IP20
- Grid dimension 18.9 mm
- Signal range -10 - 10 V, -20 - 20 mA, -5 - 5 V, 0 - 10 V, 0 - 20 mA, 4 - 20 mA
- Ambient temperature -5 to 50 °C
- Dimensions 18.9 mm x 76.6 mm x 124.3 mm
Applications
Used in automation solutions based on the Festo CPX-E series. Ambient temperature -5 to 50 °C, protection IP20.
Technical data
| Feature | Value |
|---|---|
| Type | CPX-E-4AO-U-I |
| Festo part number | 4080494 |
| Dimensions (W x L x H) | 18.9 mm x 76.6 mm x 124.3 mm |
| Grid dimension | 18.9 mm |
| Number of outputs | 4 |
| Diagnostics via LED | error per channel, error per module |
| Diagnostics via bus | general error, short circuit/overload actuator supply, short circuit/overload analogue output, parameterisation error, above nominal range, below nominal range, undervoltage load supply |
| Module parameters | deactivate actuator supply, data format analogue outputs, short circuit diagnostics actuator supply, parameterisation error diagnostics, undervoltage diagnostics load supply, behaviour after short circuit/overload actuator supply, Behaviour after short circuit/overload at analogue output |
| Channel parameters | force channel x, enable wire break/open circuit diagnostics, enable parameterisation error diagnostics, enable overload/short circuit diagnostics, signal range per channel |
| Fuse protection (short circuit) | Internal electronic fuse per module |
| Intrinsic current consumption at nominal operating voltage load | typical 15 mA |
| Maximum residual current outputs per module | 2 A |
| Nominal operating voltage DC outputs | 24 V |
| Isolation channel - internal bus | Yes |
| Isolation channel - channel | No |
| Permissible voltage fluctuations outputs | ± 25 % |
| Power supply, connection type | 2x terminal strip |
| Power supply, connection system | Spring-loaded terminal |
| Power supply, number of pins/wires | 4 |
| Power supply, conductor diameter | 0.2 to 1.5 mm² |
| Power supply, note on conductor diameter | 0.2 - 2.5 mm² for flexible conductors without wire ferrule |
| Approval | RCM |
| CE mark (see declaration of conformity) | to EU EMC Directive |
| Vibration resistance | Transport application test with severity level 1 to FN 942017-4 and EN 60068-2-6 |
| Shock resistance | Shock test with severity level 1 to FN 942017-5 and EN 60068-2-27 |
| Corrosion resistance class CRC | 0 - no corrosion stress |
| Storage temperature | -20 to 70 °C |
| Relative air humidity | 95%, Non-condensing |
| Protection against direct and indirect contact | protective extra-low voltage (PELV) |
| Degree of protection | IP20 |
| Ambient temperature | -5 to 50 °C |
| Note on ambient temperature | -5 - 60 °C for vertical installation |
| Max address volume outputs | 8 Byte |
| Electrical connection output, function | Analogue output |
| Electrical connection output, connection type | 4x terminal strip |
| Electrical connection output, connector system | Spring-loaded terminal |
| Electrical connection output, number of connections/cores | 4 |
| Electrical connection for output, conductor cross section | 0.2 to 1.5 mm² |
| Electrical connection for output, note on conductor cross section | 0.2 - 2.5 mm² for flexible conductors without wire ferrule |
| Type of mounting | via DIN rail |
| Note on materials | contains paint-wetting impairment substances (LABS), RoHS compliant |
| Material housing | PA |
| Intrinsic current consumption at nominal operating voltage for electronics/sensors | typical 60 mA |
| Nominal DC operating voltage, electronics/sensors | 24 V |
| Permissible voltage fluctuations for electronics/sensors | ± 25 % |
| Measured variable | Voltage, Current |
| Repetition accuracy | ±0.05 % at 25 °C |
| Operating error limit related to the ambient temperature range | ±0.3 % |
| Basic error limit at 25 °C | ±0.1 % |
| Power failure bridging | 10 ms |
| Analog input | -10 - 10 V, -20 - 20 mA, -5 - 5 V, 0 - 10 V, 0 - 20 mA, 4 - 20 mA |
| Data format | 15 bits + prefix, Linear scaling |
| Maximum cable length | 30 m, Shielded |
| Electrical connection for output 2, function | functional earth |
| Electrical connection for output 2, connection type | Terminal strip |
| Electrical connection for output 2, connection technology | Spring-loaded terminal |
| Electrical connection output 2, number of pins/wires | 4 |
| Electrical connection output 2, pin allocation | 009958 |
| Weight (price list) | 0.11 kg |
| Weight | 0.11 kg |
| Manufacturer | Festo |
| Hersteller-Nr | CPX-E-4AO-U-I |
| EAN | 4052568291143 |
| Zolltarifnummer | 85389099 |
| GPSR Herstellerdaten | Festo Vertrieb GmbH&Co. KG, Festo Campus 1, DE-73734 Esslingen, festo.com |
| Artikelzustand | New |
| Artikel-Authentizität | Original product |
| Material | Polyamide (PA) |
| Operating conditions | EN 60068-2-27, EN 60068-2-6 |
| Series | CPX |
| Protection rating | IP20 |
| Temperature (max.) | 50 |
Downloads
Accessories
Bus module CPX-E series IP20 control technology CPX-E-PN - Festo 4080497
Item FES-4080497Questions about this item
Any other question?
Send us the item number and your question. We clarify technical details directly with the manufacturer and usually reply on the next working day.