Images are examples, some edited with AI. The technical data are authoritative. AI notice
Analogue input module 4 inputs IP20 CPX-E-4AI-U-I - Festo 4080493
Festo analogue input module CPX-E-4AI-U-I at a glance: 4 inputs, degree of protection IP20, grid dimension 18.9 mm. As part of the CPX-E series, the module extends the periphery of a controller with additional channels.
Available
- Specialist dealer since 2009
- Invoice payment for regular customers
- Worldwide shipping
- Technical questions clarified with the manufacturer
Description
The CPX-E-4AI-U-I belongs to the Festo CPX-E series. As part of the CPX-E series, the module extends the periphery of a controller with additional channels.
Benefits
- 4 inputs
- Degree of protection IP20
- Grid dimension 18.9 mm
- Signal range -10 - 10 V and more
- Ambient temperature -5 to 50 °C
- Dimensions 18.9 mm x 76.6 mm x 124.3 mm
Applications
Used in automation solutions based on the Festo CPX-E series. Ambient temperature -5 to 50 °C, protection IP20.
Technical data
| Feature | Value |
|---|---|
| Type | CPX-E-4AI-U-I |
| Festo part number | 4080493 |
| Dimensions (W x L x H) | 18.9 mm x 76.6 mm x 124.3 mm |
| Grid dimension | 18.9 mm |
| Diagnostics via LED | error per channel, error per module |
| Diagnostics via bus | wire break, short circuit/overload sensor supply, parameter error, parameterisation error, overload analogue inputs, upper limit not met, underflow/overflow, lower limit not met |
| Module parameters | data format analogue inputs, short circuit diagnostics sensor supply, parameterisation error diagnostics, overload diagnostics analogue inputs, hysteresis limit monitoring, deactivate sensor supply, behaviour after overload analogue inputs, behaviour after short circuit/overload |
| Channel parameters | wire break diagnostics, upper limit diagnostics, parameter error diagnostics, lower limit diagnostics, underflow/overflow diagnostics, smoothing factor, signal range per channel, Lower/upper limits |
| Fuse protection (short circuit) | Internal electronic fuse per module |
| Isolation channel - internal bus | Yes |
| Isolation channel - channel | No |
| Approval | RCM |
| CE mark (see declaration of conformity) | to EU EMC Directive |
| Vibration resistance | Transport application test with severity level 1 to FN 942017-4 and EN 60068-2-6 |
| Shock resistance | Shock test with severity level 1 to FN 942017-5 and EN 60068-2-27 |
| Corrosion resistance class CRC | 0 - no corrosion stress |
| Storage temperature | -20 to 70 °C |
| Relative air humidity | 95%, Non-condensing |
| Degree of protection | IP20 |
| Ambient temperature | -5 to 50 °C |
| Note on ambient temperature | -5 - 60 °C for vertical installation |
| Type of mounting | via DIN rail |
| Note on materials | contains paint-wetting impairment substances (LABS), RoHS compliant |
| Material housing | PA |
| Number of inputs | 4 |
| Maximum residual current of inputs per module | 1.4 A |
| Nominal DC operating voltage, electronics/sensors | 24 V |
| Permissible voltage fluctuations for electronics/sensors | ± 25 % |
| Max address volume inputs | 8 Byte |
| Electrical connection input, function | Analogue input |
| Electrical connection input, connection type | 4x terminal strip |
| Electrical connection input, connector system | Spring-loaded terminal |
| Electrical connection input, number of connections/cores | 4 |
| Electrical connection for input, conductor cross section | 0.2 to 1.5 mm² |
| Electrical connection for input, note on conductor cross section | 0.2 - 2.5 mm² for flexible conductors without wire ferrule |
| Measured variable | Voltage, Current |
| Repetition accuracy | ±0.1 % at 25 °C |
| Operating error limit related to the ambient temperature range | ±0.3 % |
| Basic error limit at 25 °C | ±0.2 % |
| Power failure bridging | 10 ms |
| Analog input | -10 - 10 V, -20 - 20 mA, -5 - 5 V, 0 - 10 V, 0 - 20 mA, 1 - 5 V, 4 - 20 mA |
| Data format | 15 bits + prefix, Linear scaling |
| Maximum cable length | 30 m, Shielded |
| Electrical connection input 2, function | functional earth |
| Electrical connection input 2, connection type | Terminal strip |
| Electrical connection input 2, connection technology | Spring-loaded terminal |
| Electrical connection input 2, number of pins/wires | 4 |
| Electrical connection input 2, pin allocation | 00995842 |
| Electrical connection input 2, conductor cross-section | 0.2 to 1.5 mm² |
| Electrical connection input 2, note on conductor cross-section | 0.2 - 2.5 mm² for flexible conductors without wire ferrule |
| Weight (price list) | 0.11 kg |
| Weight | 0.11 kg |
| Manufacturer | Festo |
| Hersteller-Nr | CPX-E-4AI-U-I |
| EAN | 4052568291136 |
| Zolltarifnummer | 85389099 |
| GPSR Herstellerdaten | Festo Vertrieb GmbH&Co. KG, Festo Campus 1, DE-73734 Esslingen, festo.com |
| Artikelzustand | New |
| Artikel-Authentizität | Original product |
| Material | Polyamide (PA) |
| Operating conditions | EN 60068-2-27, EN 60068-2-6 |
| Series | CPX |
| Protection rating | IP20 |
| Temperature (max.) | 50 |
Downloads
Accessories
Bus module CPX-E series IP20 control technology CPX-E-PN - Festo 4080497
Item FES-4080497Questions about this item
Any other question?
Send us the item number and your question. We clarify technical details directly with the manufacturer and usually reply on the next working day.