Everis LQ8 is the largest CPC LQ series: couplings with 1/2" flow for cooling loops that move a lot of coolant, such as rack manifolds or the connection to a CDU. The valve disconnects without drips even under pressure, redundant seals protect the connected joint over long periods, and an audible click confirms engagement. Bodies are chrome-plated brass with EPDM seals for water-glycol, pressure range is vacuum to 8.3 bar and temperature -17 to 115 °C. Terminations: 15.9 mm (5/8") locking hose barb, SAE-12 and G3/4 male thread.
- 6 items
- 1 manufacturer
- Net prices plus VAT
Buying guide
How to choose Everis LQ8
What matters when choosing: properties, comparison and typical applications.
Selection criteria
| Criterion | Everis LQ8 |
|---|---|
| Flow size | 1/2" |
| Pressure range | Vacuum to 8.3 bar |
| Temperature | -17 to 115 °C |
| Body | Chrome-plated brass |
| Seal | EPDM, for water-glycol |
| Terminations | Locking hose barb 15.9 mm (5/8"), SAE-12 male thread 3/4", G3/4 male thread (BSPP) |
| Design | Coupling body and insert, in-line |
Frequently asked questions
- When should I choose LQ8 over LQ6?
- When the loop needs more flow: LQ8 is sized for 1/2" flow, LQ6 for 3/8". The low pressure drop keeps pump effort down.
- Can LQ8 be disconnected under pressure?
- Yes. Both halves shut on disconnection and nothing drips, so servers or manifolds can be swapped without draining the cooling loop.
- Which coolants are intended?
- The EPDM seal is designed for common water-glycol mixtures.
- What is the locking hose barb for?
- It holds reinforced tubing without an extra clamp. For a threaded joint choose SAE-12 or G3/4 male thread.