Images are examples, some edited with AI. The technical data are authoritative. AI notice
Pressure sensor 0 to 10 bar, 2x PNP/NPN, IO-Link, with display SPAU-P10R-T-G18FD-L-PNLK-PNVBA-M12U - Festo 595878
The pressure sensor SPAU-P10R-T-G18FD-L-PNLK-PNVBA-M12U measures relative pressure in the range 0 to 10 bar and switches via 2 switching outputs, PNP/NPN switchable, plus analogue output 0 to 10 V, 4 to 20 mA or 1 to 5 V. Illuminated LCD with LED, setting via teach-in, display and keys or IO-Link.
- Specialist dealer since 2009
- Invoice payment for regular customers
- Worldwide shipping
- Technical questions clarified with the manufacturer
Description
Measuring range 0 to 10 bar: the Festo pressure sensor SPAU-P10R-T-G18FD-L-PNLK-PNVBA-M12U measures relative pressure and switches via 2 switching outputs, PNP/NPN switchable, plus analogue output 0 to 10 V, 4 to 20 mA or 1 to 5 V. Operating medium for SPAU-P10R-T-G18FD-L-PNLK-PNVBA-M12U: compressed air and inert gases, medium temperature 0 to 50 °C.
Benefits
- Measuring range 0 to 10 bar, overload range up to 15 bar
- Accuracy 1.5 %FS, repeatability ± 0.3 %FS
- Degree of protection IP65, IP67, ambient temperature 0 to 50 °C
- G1/8 port, electrical: M12x1 plug (4-pin)
- 2 switching outputs, PNP/NPN switchable, N/C or N/O switchable, output current up to 100 mA
- Rise time 3 ms, operating voltage 20 to 30 V DC
Application
Typical tasks include monitoring supply and working pressure on machines and in compressed air networks. Mounting is directly via the thread, in any mounting position.
Technical data
| Type | SPAU-P10R-T-G18FD-L-PNLK-PNVBA-M12U |
|---|---|
| Approval | RCM, c UL us - Listed (OL) |
| CE mark (see declaration of conformity) | To EU EMC Directive, in accordance with EU RoHS Directive |
| UKCA marking (see declaration of conformity) | To UK RoHS regulations |
| KC mark | KC-EMV |
| Note on materials | RoHS compliant |
| Measured variable | Relative pressure |
| Measurement method | Piezoresistive pressure sensor |
| Start value for pressure measuring range | 0 bar |
| End value for pressure measuring range | 10 bar |
| Overload pressure | 15 bar |
| Operating medium | Compressed air to ISO 8573-1:2010 [7:4:4], inert gas |
| Note on operating and pilot medium | Lubricated operation possible |
| Media temperature | 0 to 50 °C |
| Ambient temperature | 0 to 50 °C |
| Resolution ADC | 12 bit |
| Accuracy in ± % FS | 1.5 %FS |
| Repetition accuracy in ± %FS | 0.3 %FS |
| Temperature coefficient in ± %FS/K | 0.05 %FS/K |
| Switching output | 2 x PNP or 2 x NPN, switchable, 2xPNP |
| Switching function | Freely programmable |
| Switching element function | NC or NO, switchable |
| Maximum output current | 100 mA |
| Analogue output | 0 - 10 V, 4 - 20 mA, 1 - 5 V |
| Rise time | 3 ms |
| Maximum load resistance current output | 500 Ohm |
| Minimum load resistance voltage output | 10 kOhm |
| Short circuit current rating | Yes |
| Overload protection | Yes |
| Protocol | IO-Link |
| IO-Link, Protocol version | Device V 1.1 |
| IO-Link, Profile | Smart sensor profile |
| IO-Link, Function classes | Binary data channel (BDC), process data variable (PDV), identification, diagnostics, teach channel |
| IO-Link, communication mode | COM2 (38.4 kBaud) |
| IO-Link, SIO-Mode support | Yes |
| IO-Link, Port class | A |
| IO-Link, Process data length OUT | 0 bytes |
| IO-Link, Process data length IN | 2 bytes |
| IO-Link, Process data content IN | 14 bit PDV (pressure measurement value), 2 bit BDC (pressure monitoring) |
| IO-Link, Min. cycle time | 3 ms |
| IO-Link, Data storage required | 500 byte |
| Operational voltage range DC | 20 to 30 V |
| Reverse polarity protection | For all electrical connections |
| Electrical connection 1, connection type | Plug |
| Electrical connection 1, connector system | M12x1, A-coded to EN 61076-2-101 |
| Electrical connection 1, number of connections/cores | 4 |
| Electrical connection 1, type of mounting | Not rotatable |
| Electrical connection 1, compatible type of mounting | Compatible with rotatable screw-type lock |
| Type of mounting | With thread |
| Mounting position | Any |
| Pneumatic connection | G1/8 |
| Product weight | 70 g |
| Material in contact with the medium | High-alloy stainless steel |
| Display type | Illuminated LCD, LED |
| Setting options | IO-Link, Teach-in, via display and buttons |
| Protection against tampering | IO-Link, PIN code |
| Setting range threshold value | 0 to 100 % |
| Setting range hysteresis | 0 to 90 % |
| Degree of protection | IP65, IP67 |
| Corrosion resistance class CRC | 2 - Moderate corrosion stress |
| LABS (PWIS) conformity | VDMA24364-B1/B2-L |
| Weight | 0.09 kg |
| Manufacturer | Festo |
| Hersteller-Nr | SPAU-P10R-T-G18FD-L-PNLK-PNVBA-M12U |
| EAN | 4052568404321 |
| Zolltarifnummer | 90262020 |
| GPSR Herstellerdaten | Festo Vertrieb GmbH&Co. KG, Festo Campus 1, DE-73734 Esslingen, festo.com |
| Artikelzustand | New |
| Artikel-Authentizität | Original product |
| Thread | G 1/8 |
| Measuring range max. [bar] | 10 |
| Protection rating | IP65 |
| Temperaturbereich | 0-50 °C |
| Temperature (max.) | 50 |
Downloads
Questions about this item
Any other question?
Send us the item number and your question. We clarify technical details directly with the manufacturer and usually reply on the next working day.