Images are examples, some edited with AI. The technical data are authoritative. AI notice
PROFINET interface CPX-AP-A-PN-FO - Festo 8129246
- Specialist dealer since 2009
- Invoice payment for regular customers
- Worldwide shipping
- Technical questions clarified with the manufacturer
Technical data
| Dimensions (W x L x H) | 50.1 mm x 107.3 mm x 94.2 mm |
|---|---|
| Grid dimension | 50.1 mm |
| Type of mounting | Screw-clamped |
| Max. number of modules | 80 |
| Product weight | 182 g |
| Mounting position | Any |
| Ambient temperature | -20 ... 50 °C |
| Note on ambient temperature | Observe ambient temperature derating according to IEC 61131-2:2017 |
| Storage temperature | -20 ... 70 °C |
| Relative air humidity | 5 - 95%, Non-condensing |
| Nominal altitude of use | <= 2000 m ASL (> 79.5 kPa) |
| Max. installation height | 3500 m |
| Note on max. installation height | Observe ambient temperature derating according to IEC 61131-2:2017 |
| Corrosion resistance class CRC | 1 - Low corrosion stress |
| Vibration resistance | Transport application test with severity level 2 to FN 942017-4 and EN 60068-2-6 |
| Note on vibration resistance | Transport application test with severity class 1 to FN 942017-4 and EN 60068-2-6 |
| Shock resistance | Shock test with severity level 2 to FN 942017-5 and EN 60068-2-27 |
| Note on shock resistance | 30 g/11 ms to EN 60068-2-27, SG1 on DIN rail, SG2 on direct mounting, Shock test with severity level 1 to FN 942017-5 and EN 60068-2-27 |
| Protection class | III |
| Pollution degree | 2 |
| Overvoltage category | II |
| Max. cable length | 50 m PROFINET |
| LABS (PWIS) conformity | VDMA24364-B2-L |
| Fire test material | UL94 V-0 (housing) |
| Note on materials | RoHS compliant, Free of halogen, Free of phosphoric acid ester |
| Material cover | Reinforced PBT |
| Material flange | Nickel-plated die-cast zinc |
| Material screws | Nickel-plated steel |
| Material threaded sleeve | High-alloy stainless steel |
| Material seals | NBR |
| Material o-ring | Fluoro rubber |
| Diagnostics via LED | Diagnostics per module, PROFINET communication, Power supply, electronics/sensors, Load power supply, System diagnostics, Maintenance required |
| Diagnostics via bus | Electronics/sensors overvoltage, Load overvoltage, Electronics/sensors undervoltage, Load undervoltage |
| Fieldbus interface | Ethernet |
| Field bus, protocol | LLDP, MRP, MRPD (ring redundancy), PROFINET FSU, PROFINET I&M0 .. 3, PROFINET IRT, PROFINET RT, PROFINET shared device, S2 system redundancy, SNMP |
| Fieldbus interface, function | Bus connection incoming/outgoing |
| Field bus, connection type | 2x socket |
| Field bus, connection system | SCRJ according to IEC 61754-24-21 |
| Fieldbus interface, connection pattern | 00995771 |
| Field bus, connection pattern | 2 |
| Field bus interface, electrical isolation | Yes |
| Field bus interface, transmission rate | 100 Mbit/s |
| Fieldbus interface, note on transmission rate | 100 Mbit, fast switching Ethernet |
| Max. address volume, inputs | 1024 byte |
| Max. address volume, outputs | 1024 byte |
| Module parameters | Configuration of voltage monitoring load supply PL |
| Internal cycle time | < 1 ms |
| Configuration support | GSDML file |
| Communication interface, function | System communication XF20 OUT |
| Communication interface, connection type | Socket |
| Communication interface, connection technology | M8x1, D-coded according to EN 61076-2-114 |
| Communication interface, number of pins/cores | 4 |
| Communication interface, plug pattern | 00995937 |
| Communication interface, protocol | AP |
| Communication interface, screened | Yes |
| Note regarding operating voltage | SELV/PELV fixed power supplies required, Note the voltage drop |
| Note on nominal operating voltage DC | Protected Extra-Low-Voltage to IEC 60204-1 |
| Nominal operating voltage DC of load | 24 V |
| Permissible voltage fluctuation of load | ±25% |
| Nominal DC operating voltage, electronics/sensors | 24 V |
| Permissible voltage fluctuations for electronics/sensors | ±25% |
| Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 115 mA |
| Intrinsic current consumption at nominal operating voltage load | Typically 4 mA |
| Power failure bridging | 10 ms |
| Potential separation between the supply voltages electronics/sensor technology and load/valves | Yes |
| Reverse polarity protection | Yes |
| Manufacturer | Festo |
| Hersteller-Nr | CPX-AP-A-PN-FO |
| EAN | 4052568650742 |
| Zolltarifnummer | 85176200 |
| GPSR Herstellerdaten | Festo Vertrieb GmbH&Co. KG, Festo Campus 1, DE-73734 Esslingen, festo.com |
| Artikelzustand | New |
| Artikel-Authentizität | Original product |
Downloads
Questions about this item
Any other question?
Send us the item number and your question. We clarify technical details directly with the manufacturer and usually reply on the next working day.