Images are examples, some edited with AI. The technical data are authoritative. AI notice
Pressure sensor 0 to 12 bar with IO-Link G1/8 SPAU-P12R-H-G18FD-L-PNLK-PNVBA-M12U - Festo 8182149
The Festo pressure sensor SPAU-P12R-H-G18FD-L-PNLK-PNVBA-M12U monitors relative pressure within 0 to 12 bar and switches via two switching outputs, PNP or NPN selectable. Besides the analogue output 0 - 10 V, 4 - 20 mA, 1 - 5 V, IO-Link is available as a digital interface. The pneumatic connection is a G1/8 port, the electrical connection an M12x1 plug, 4-pin.
- Specialist dealer since 2009
- Invoice payment for regular customers
- Worldwide shipping
- Technical questions clarified with the manufacturer
Description
Where relative pressure has to be monitored within 0 to 12 bar, the SPAU-P12R-H-G18FD-L-PNLK-PNVBA-M12U provides switching signals and measured value from a single device.
Benefits
- Measuring range 0 to 12 bar, overload pressure 15 bar
- Accuracy ±1.5 %FS, repetition accuracy ±0.3 %FS
- Two switching outputs, PNP or NPN selectable, switching function freely programmable
- Analogue output 0 - 10 V, 4 - 20 mA, 1 - 5 V and IO-Link Device V 1.1
- Illuminated LCD with LED, setting via IO-Link, teach-in, via display and buttons
- Degree of protection IP65, IP67, corrosion resistance class 2 (moderate corrosion stress)
Applications
Operating medium of the SPAU-P12R-H-G18FD-L-PNLK-PNVBA-M12U: compressed air to ISO 8573-1:2010 [7:4:4], inert gas, mounting via din rail. Typical tasks up to 12 bar include monitoring supply and working pressure in compressed air systems. Supply voltage 20 to 30 V DC.
Technical data
| Type | SPAU-P12R-H-G18FD-L-PNLK-PNVBA-M12U |
|---|---|
| Festo part number | 8182149 |
| Approval | RCM, c UL us - Listed (OL) |
| CE mark (see declaration of conformity) | To EU EMC Directive, In accordance with EU RoHS Directive |
| UKCA marking (see declaration of conformity) | To UK RoHS instructions |
| KC mark | KC-EMV |
| Note on materials | RoHS compliant |
| Measured variable | Relative pressure |
| Measurement method | Piezoresistive pressure sensor |
| Start value for pressure measuring range | 0 bar |
| End value for pressure measuring range | 12 bar |
| Overload pressure | 15 bar |
| Operating medium | Compressed air to ISO 8573-1:2010 [7:4:4], Inert gas |
| Note on operating and pilot medium | Lubricated operation possible |
| Media temperature | 0 to 50 °C |
| Ambient temperature | 0 to 50 °C |
| Resolution ADC | 12 bit |
| Accuracy in ± % FS | 1.5 %FS |
| Repetition accuracy in ± %FS | 0.3 %FS |
| Temperature coefficient in ± %FS/K | 0.05 %FS/K |
| Switching output | 2 x PNP or 2 x NPN, switchable, 2xPNP |
| Switching function | Freely programmable |
| Switching element function | NC or NO, switchable |
| Max. output current | 100 mA |
| Analogue output | 0 - 10 V, 4 - 20 mA, 1 - 5 V |
| Rise time | 3 ms |
| Max. load resistance current output | 500 Ohm |
| Min. load resistance voltage output | 10 kOhm |
| Short circuit current rating | Yes |
| Overload protection | Yes |
| Protocol | IO-Link |
| IO-Link, protocol version | Device V 1.1 |
| IO-Link, profile | Smart sensor profile |
| IO-Link, function classes | Binary data channel (BDC), Process data variable (PDV), Identification, Diagnostics, Teach channel |
| IO-Link, communication mode | COM2 (38.4 kBaud) |
| IO-Link, SIO mode support | Yes |
| IO-Link, Port class | A |
| IO-Link, process data width OUT | 0 bytes |
| IO-Link, process data width IN | 2 bytes |
| IO-Link, process data content IN | 14 bit PDV (pressure measurement value), 2 bit BDC (pressure monitoring) |
| IO-Link, minimum cycle time | 3 ms |
| IO-Link, data storage required | 500 byte |
| Operational voltage range DC | 20 to 30 V |
| Reverse polarity protection | For all electrical connections |
| Electrical connection 1, connection type | Plug |
| Electrical connection 1, connector system | M12x1, A-coded to EN 61076-2-101 |
| Electrical connection 1, number of connections/cores | 4 |
| Electrical connection 1, type of mounting | Not rotatable |
| Electrical connection 1, compatible type of mounting | Compatible with rotatable screw-type lock |
| Type of mounting | via DIN rail |
| Mounting position | Any |
| Pneumatic connection | G1/8 |
| Product weight | 70 g |
| Material in contact with the medium | High-alloy stainless steel |
| Display type | Illuminated LCD, LED |
| Setting options | IO-Link, Teach-in, Via display and buttons |
| Protection against tampering | IO-Link, PIN code |
| Setting range threshold value | 0 to 100 % |
| Setting range hysteresis | 0 to 90 % |
| Degree of protection | IP65, IP67 |
| Corrosion resistance class CRC | 2 - Moderate corrosion stress |
| LABS (PWIS) conformity | VDMA24364-B1/B2-L |
| Weight | 0.09 kg |
| Manufacturer | Festo |
| Hersteller-Nr | SPAU-P12R-H-G18FD-L-PNLK-PNVBA-M12U |
| EAN | 4052568616748 |
| Zolltarifnummer | 90262020 |
| GPSR Herstellerdaten | Festo Vertrieb GmbH&Co. KG, Festo Campus 1, DE-73734 Esslingen, festo.com |
| Artikelzustand | New |
| Artikel-Authentizität | Original product |
| Thread | G 1/8 |
| Measuring range max. [bar] | 12 |
| Medientemperatur [°C] | 0 bis 50 |
| Series | SPAU |
| Protection rating | IP65 |
| Temperaturbereich | 0-50 °C |
| Temperature (max.) | 50 |
Downloads
Questions about this item
Any other question?
Send us the item number and your question. We clarify technical details directly with the manufacturer and usually reply on the next working day.






