Images are examples, some edited with AI. The technical data are authoritative. AI notice
Bus node for CTEU, EtherNet/IP, Modbus TCP protocol, 24 V DC, IP65 CTEU-EP-EX1C - Festo 8107591
The Festo bus node CTEU-EP-EX1C connects the CTEU series to the higher-level controller. Key data: EtherNet/IP, Modbus TCP protocol, nominal operating voltage 24 V DC and internal cycle time 1 ms per 1 byte of user data. It also offers IP65/IP67 protection and ambient temperature 0 to 50 °C.
- Specialist dealer since 2009
- Invoice payment for regular customers
- Worldwide shipping
- Technical questions clarified with the manufacturer
Description
The bus node CTEU-EP-EX1C connects the CTEU series to the higher-level controller. The main data are EtherNet/IP, Modbus TCP protocol and nominal operating voltage 24 V DC.
Advantages
- Fieldbus connection via EtherNet/IP, Modbus TCP
- Nominal operating voltage 24 V DC
- Internal cycle time 1 ms per 1 byte of user data
- IP65/IP67 protection for mounting directly on the machine
- Suitable for ambient temperatures of 0 to 50 °C
- For potentially explosive areas: Ex ec IIC Gc X
Application
CTEU-EP-EX1C is used when designing, extending and maintaining installations with the CTEU series.
Technical data
| Type | CTEU-EP-EX1C |
|---|---|
| Festo part number | 8107591 |
| Protocol | EtherNet/IP, Modbus TCP |
| Dimensions (W x L x H) | 40 mm x 91 mm x 50 mm |
| Product weight | 98 g |
| Ambient temperature | 0 to 50 °C |
| Storage temperature | -20 to 70 °C |
| Degree of protection | IP65, IP67 |
| Corrosion resistance class CRC | 2 - Moderate corrosion stress |
| LABS (PWIS) conformity | VDMA24364 zone III |
| CE mark (see declaration of conformity) | To EU EMC Directive, In accordance with EU RoHS Directive |
| UKCA marking (see declaration of conformity) | To UK RoHS instructions |
| Approval | RCM, c UL us - Listed (Oil) |
| Explosion protection | Class I, Div. 2 (CA), Class I, Div. 2 (US), Class II, Div. 2 (CA), Class II, Div. 2 (US), Zone 0 (BR), Zone 2 (ATEX), Zone 2 (CA), Zone 2 (CN), Zone 2 (IEC-EX), Zone 2 (KR), Zone 2 (UKEX), Zone 2 (US), Zone 22 (ATEX), Zone 22 (BR), Zone 22 (CA), Zone 22 (CN), Zone 22 (IEC-EX), Zone 22 (KR), Zone 22 (UKEX), Zone 22 (US) |
| ATEX category gas | II 3G |
| ATEX category dust | II 3D |
| Explosion protection certification outside the EU | EPL Dc (KR), EPL Dc (US), EPL Ga (BR), EPL Gc (CA), EPL Gc (CN), EPL Gc (GB), EPL Gc (IECEx), EPL Gc (KR), EPL Gc (US) |
| Explosion ignition protection type for gas | Ex ec IIC Gc X |
| Explosion ignition protection type for dust | Ex tc IIIC Dc X |
| Explosion ambient temperature | -5°C ≤ Ta ≤ +50°C |
| Certificate issuing authority | DNV 23.0350 X/00, IECEx IBE 17.0003 X, KTL 24-KA4BO-0392X, KTL 24-KA4BO-0393X, KTL 24-KA4BO-0394X, KTL 24-KA4BO-0395X, NEPSI GYJ19.1188X, SITIIAS CCC 202032230700686, UL E239998 |
| Note on materials | RoHS compliant |
| Material housing | PA |
| LED display, product-specific | PS: Operating voltage for electronics and load supply, X1: System status of module at I-Port 1, X2: System status of module at I-Port 2 |
| LED display, bus-specific | NS: Network status, TP1: Network active port 1, TP2: Network active port 2 |
| Diagnosis | Communication error, System diagnostics, Undervoltage |
| Operator controls | DIL switch |
| Field bus interface | 2x socket, M12x1, 4-pin, D-coded |
| Max. address volume, inputs | 64 byte |
| Max. address volume, outputs | 64 byte |
| Parameterisation | Diagnostic behaviour, Fail-safe and idle response |
| Baud rate | 10/100 Mbit/s |
| Internal cycle time | 1 ms per 1 byte of user data |
| Configuration support | EDS file |
| Additional functions | IP addressing via DHCP, DIL switch, fieldbus or FFT, Integrated switch, Ring topology (DLR), SNMP, Start-up parameterisation in plain text via fieldbus, System status can be mapped using process data, Web server |
| Operational voltage range DC | 18 to 30 V |
| Nominal operating voltage DC | 24 V |
| Max. power supply | 4 A |
| Intern power consumption nominal operating voltage | Typ. 65 mA |
| Manufacturer | Festo |
| Hersteller-Nr | CTEU-EP-EX1C |
| EAN | 4052568605681 |
| Zolltarifnummer | 85176200 |
| GPSR Herstellerdaten | Festo Vertrieb GmbH&Co. KG, Festo Campus 1, DE-73734 Esslingen, festo.com |
| Artikelzustand | New |
| Artikel-Authentizität | Original product |
| Housing material | PA |
| Operating voltage | 24 V DC |
| Series | CTEU |
| Protection rating | IP65 |
| Temperaturbereich | 0-50 °C |
| Temperature (max.) | 50 |