Images are examples, some edited with AI. The technical data are authoritative. AI notice
Analogue input module CPX-AP-A-4AI-U-I-RTD-M12 - Festo 8129113
Net
excl. VAT
€241.92
Item
FES-8129113
Manufacturer no.
CPX-AP-A-4AI-U-I-RTD-M12
- Specialist dealer since 2009
- Invoice payment for regular customers
- Worldwide shipping
- Technical questions clarified with the manufacturer
Technical data
| Dimensions (W x L x H) | 50.1 mm x 107.3 mm x 57.5 mm |
|---|---|
| Grid dimension | 50.1 mm |
| Type of mounting | Screw-clamped |
| Product weight | 121 g |
| Mounting position | Any |
| Ambient temperature | -20 ... 50 °C |
| Note on ambient temperature | Observe ambient temperature derating according to IEC 61131-2:2017 |
| Storage temperature | -20 ... 70 °C |
| Relative air humidity | 5 - 95%, Non-condensing |
| Nominal altitude of use | <= 2000 m ASL (> 79.5 kPa) |
| Max. installation height | 3500 m |
| Note on max. installation height | Observe ambient temperature derating according to IEC 61131-2:2017 |
| Corrosion resistance class CRC | 1 - Low corrosion stress |
| Vibration resistance | Transport application test with severity level 2 to FN 942017-4 and EN 60068-2-6 |
| Note on vibration resistance | Transport application test with severity class 1 to FN 942017-4 and EN 60068-2-6 |
| Shock resistance | Shock test with severity level 2 to FN 942017-5 and EN 60068-2-27 |
| Note on shock resistance | 30 g/11 ms to EN 60068-2-27, SG1 on DIN rail, SG2 on direct mounting, Shock test with severity level 1 to FN 942017-5 and EN 60068-2-27 |
| Protection class | III |
| Pollution degree | 2 |
| Overvoltage category | II |
| Max. cable length | 30 m inputs |
| LABS (PWIS) conformity | VDMA24364-B2-L |
| Fire test material | UL94 V-0 (housing) |
| Note on materials | RoHS compliant, Free of halogen, Free of phosphoric acid ester |
| Material cover | Reinforced PBT |
| Material screws | Nickel-plated steel |
| Material threaded sleeve | High-alloy stainless steel |
| Material o-ring | Fluoro rubber |
| Diagnostics via LED | Diagnostics per module, Status per channel |
| Diagnostics per internal communication | Wire breakage, Communication error, Short circuit/overload, Parameter error, Parameterisation error, Overload analogue inputs, Upper limit value violated, Electronics/sensors overvoltage, Underflow/overflow, Lower limit value not observed, Electronics/sensors undervoltage |
| Max. address volume, inputs | 8 byte |
| Channel parameters | Measured value smoothing, Analog input, Lower/upper limits, Linear scaling activation, Unit for temperature measurement, Hysteresis for measured value monitoring |
| Communication interface, protocol | AP |
| Note regarding operating voltage | SELV/PELV fixed power supplies required, Note the voltage drop |
| Note on nominal operating voltage DC | Protected Extra-Low-Voltage to IEC 60204-1 |
| Nominal DC operating voltage, electronics/sensors | 24 V |
| Permissible voltage fluctuations for electronics/sensors | ±25% |
| Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 34 mA |
| Power failure bridging | 10 ms |
| Reverse polarity protection | Yes |
| Electrical connection input, function | Analogue input |
| Electrical connection input, connection type | 4x socket |
| Electrical connection input, connector system | M12x1, A-coded to EN 61076-2-101 |
| Electrical connection input, number of connections/cores | 5 |
| Electrical connection input, connection pattern | 00995384 |
| Number of inputs | 4 |
| Electrical isolation of inputs between channel – internal communication | Yes |
| Behaviour after end of overload of the sensor supply | Automatic return |
| Fuse protection of inputs (short circuit) | Internal electronic fuse per module |
| Max. residual current of inputs per module | 1 A |
| Electrical isolation of inputs between channels | No |
| Measured variable | Voltage, Current, Temperature, Resistor |
| Note on the measured variable | Temperature: PT100 and NI100 supported |
| Data format | 15 bits + prefix, Linear scaling |
| analog input | -10 - 10 V, -5 - 5 V, 0 - 10 V, 1 - 5 V, 0 - 20 mA, 4 - 20 mA, 0 - 500 Ohm |
| Repetition accuracy | ±0.025% at 25°C |
| Basic error limit at 25 °C | ±0.1% for voltage, ±0.1 % for voltage, ±0.4% for temperature, ±0.2 % for resistance |
| Operating error limit related to the ambient temperature range | ±0.15% for voltage, ±0.15% for current, ±0.9 % for temperature, ±0.35% for resistor |
| Max. power supply per channel | 0.5 A |
| Manufacturer | Festo |
| Hersteller-Nr | CPX-AP-A-4AI-U-I-RTD-M12 |
| EAN | 4052568784584 |
| Zolltarifnummer | 85389099 |
| GPSR Herstellerdaten | Festo Vertrieb GmbH&Co. KG, Festo Campus 1, DE-73734 Esslingen, festo.com |
| Artikelzustand | New |
| Artikel-Authentizität | Original product |
Downloads
Questions about this item
Any other question?
Send us the item number and your question. We clarify technical details directly with the manufacturer and usually reply on the next working day.