Images are examples, some edited with AI. The technical data are authoritative. AI notice
Input module for CPX terminal, HART protocol, 24 V DC, grid dimension 50 mm CPX-4AE-4AA-H - Festo 8059847
The input module CPX-4AE-4AA-H is a genuine Festo part for the CPX terminal. Festo specifies HART protocol, nominal operating voltage 24 V DC and power failure bridging 10 ms. Further data: ambient temperature -5 to 50 °C and grid dimension 50 mm.
- Specialist dealer since 2009
- Invoice payment for regular customers
- Worldwide shipping
- Technical questions clarified with the manufacturer
Description
The input module CPX-4AE-4AA-H is a genuine Festo part for the CPX terminal. The main data are HART protocol and nominal operating voltage 24 V DC.
Advantages
- Fieldbus connection via HART
- Nominal operating voltage 24 V DC
- Power failure bridging 10 ms
- Suitable for ambient temperatures of -5 to 50 °C
- Grid dimension 50 mm
- Dimensions 50 mm x 107 mm x 70 mm (incl. interlinking block and connection technology) (W x L x H)
Application
CPX-4AE-4AA-H is used when designing, extending and maintaining installations with the CPX terminal.
Technical data
| Type | CPX-4AE-4AA-H |
|---|---|
| Festo part number | 8059847 |
| Series | CPX |
| Dimensions (W x L x H) | 50 mm x 107 mm x 70 mm (incl. interlinking block and connection technology) |
| Diagnosis | Parameterisation error, wire break per channel, limit violation to NE43 per channel, limit violation per channel, short circuit/overload per channel, overflow/underflow |
| Parameterisation | Parameterisation error, signal range per channel, number of HART retries, data format, wire break per channel, fail-safe per channel, forcing per channel, limit monitoring per channel, limit violation to NE43 per channel, limit violation per channel, HART variables, hysteresis for limits, idle mode per channel, short circuit/overload per channel, measured value smoothing, overflow/underflow, wire break monitoring per channel, NE43 monitoring of inputs, overflow/underflow monitoring, behaviour after short circuit/overload |
| Operator controls | DIL switch |
| LED display | 1 Group diagnostics, 4 Channel diagnostics, 4 Channel status |
| Operational voltage range DC | 18 to 30 V |
| Internal current consumption, operating voltage | Typically 170 mA |
| Nominal operating voltage DC | 24 V |
| Power failure bridging | 10 ms |
| Isolation channel - internal bus | Yes |
| Isolation channel - channel | No |
| Corrosion resistance class CRC | (installed), 1 - Low corrosion stress |
| Storage temperature | -20 to 70 °C |
| Degree of protection | Dependent on the connection block |
| Ambient temperature | -5 to 50 °C |
| Product weight | 77.4 g |
| Protocol | HART |
| Max. cable length | 500 m |
| Note on materials | RoHS compliant |
| Material housing | Makrolon, Reinforced PA |
| Type of mounting | On interlinking block |
| Fuse protection (short circuit) | Internal electronic fuse per channel |
| CE mark (see declaration of conformity) | To EU EMC Directive |
| Reverse polarity protection | For all electrical connections |
| Relative air humidity | 95%, Non-condensing |
| Repetition accuracy | 0.05 % at 25 °C |
| Operating error limit related to the ambient temperature range | ±0.3 % |
| Basic error limit at 25 °C | ±0.1 % |
| Data format | 15 bit + sign, scalable to 15 bit |
| Sensor type | 0 - 20 mA, 4 - 20 mA, 4 - 20 mA with HART |
| Grid dimension | 50 mm |
| Number of selectable analogue inputs/outputs | 4 |
| Vibration resistance | Transport application test with severity level 2 to FN 942017-4 and EN 60068-2-6 |
| Shock resistance | Shock test with severity level 2 to FN 942017-5 and EN 60068-2-27 |
| Max. load | 750 Ohm |
| Max. input resistance | 300 Ohm |
| Max. short-circuit current | 22 mA |
| Max. open-circuit voltage | 28.8 V |
| Min. available sensor voltage | 20.7 V at 20 mA |
| Signal range | 0 - 20 mA, 4 - 20 mA, 4 - 20 mA with HART |
| Weight | 0.105 kg |
| Manufacturer | Festo |
| Hersteller-Nr | CPX-4AE-4AA-H |
| EAN | 4052568295622 |
| Zolltarifnummer | 85389099 |
| GPSR Herstellerdaten | Festo Vertrieb GmbH&Co. KG, Festo Campus 1, DE-73734 Esslingen, festo.com |
| Artikelzustand | New |
| Artikel-Authentizität | Original product |
| Material | Polyamide (PA) |
| Operating conditions | EN 60068-2-27, EN 60068-2-6 |
| Operating voltage | 24 V DC |
| Temperature (max.) | 50 |
Downloads
Accessories
Analogue module 4 inputs 0 - 20 mA, 4 - 20 mA CPX-4AE-I - Festo 541484
Item FES-541484Questions about this item
Any other question?