Images are examples, some edited with AI. The technical data are authoritative. AI notice
2/2-way solenoid valve NC, directly operated, stainless steel 1.4401, G 1/4, DN 3, 0 to 10 bar, FKM, 230 V AC/DC, ATEX - Riegler 185500
On power failure this 2/2-way solenoid valve stays shut, with 230 V AC/DC on the coil it opens the flow path. Built with a stainless steel 1.4401 housing, FKM seals and a G 1/4 port at DN 3. ATEX version according to the manufacturer. Medium temperature 0 to 90 °C, operating pressure 0 to 10 bar.
- Specialist dealer since 2009
- Invoice payment for regular customers
- Worldwide shipping
- Technical questions clarified with the manufacturer
Description
The 2/2-way solenoid valve MVA.14.ES.230.F.BD.3.EX.K controls fluids in plants via an electrical signal at 230 V AC/DC. It operates in the range 0 to 10 bar at nominal size DN 3 and is directly operated.
Benefits
- Fail-safe NC position: without 230 V AC/DC on the coil the flow path stays closed.
- ATEX version according to the manufacturer, observe the marking on the device for conditions of use.
- Switches from 0 bar: directly operated, no minimum pressure needed, operating pressure up to 10 bar.
- Materials: housing in stainless steel 1.4401, valve seat in stainless steel, internal parts in stainless steel, thread G 1/4.
- FKM seals: rated for medium temperatures of 0 to 90 °C, coil 230 V AC/DC.
- Electrics: 230 V AC/DC, terminal connection box with PCB terminal blocks, degree of protection IP 65 (with connector socket fitted).
Applications
Because the coil system is separated from the medium by a diaphragm, the manufacturer rates the series for critical media as well. Check the resistance of housing and seal to the specific medium beforehand. The ambient temperature may be 0 to 55 °C, the medium 0 to 90 °C. The NC rest position suits any G 1/4 line that has to close on power failure.
Technical data
| Type no. | MVA.14.ES.230.F.BD.3.EX.K |
|---|---|
| Design type | 2/2-way solenoid valve |
| Operation | directly operated |
| Function | normally closed (NC) |
| Port thread | G 1/4 (female) |
| Nominal size DN | 3 mm |
| Operating pressure | 0 to 10 bar |
| Medium temperature | 0 to 90 °C |
| Ambient temperature | 0 to 55 °C |
| Degree of protection | IP 65 (with connector socket fitted) |
| Electrical connection | terminal connection box with PCB terminal blocks |
| Housing | stainless steel 1.4401 |
| Valve seat | stainless steel |
| Internal parts | stainless steel |
| Seal material | FKM |
| Voltage | 230 V AC/DC |
| Version | media-separated |
| Explosion protection | ATEX version |
| Manual override | yes |
| Dimension A | 71.0 mm |
| Dimension B | 46.0 mm |
| Dimension C | 18.0 mm |
| Manufacturer | Riegler |
| Hersteller-Nr | MVA.14.ES.230.F.BD.3.EX.K |
| EAN | 4047322944830 |
| Zolltarifnummer | 84818079 |
| GPSR Herstellerdaten | Riegler & Co. KG, Schützenstraße 27, DE-72574 Bad Urach, www.riegler.de |
| Artikelzustand | New |
| Artikel-Authentizität | Original product |
| Country of Manufacture | Germany |
| Ausführung | direktgesteuert |
| Material | Stainless steel 1.4401 |
| Thread | G 1/4 |
| Nominal size DN [mm] | 3 |
| Housing material | Stainless steel 1.4401 |
| Actuation type | Electrical |
| Thread type | Internal thread |
| Medientemperatur [°C] | 0 bis 90 |
| Norm | DIN EN ISO 228-1 |
| Certification | ATEX |
| Operating voltage | 230 V AC/DC |
| Betriebsdruck max [bar] | 10 |
| Pneumatic connection | G1/4 IG |
| Protection rating | IP65 |
| Temperaturbereich | 0-90 °C |
| Temperature (max.) | 90 |